详细介绍
IIC级BJX-20/30 20/60 20/36防爆接线箱
1. 适用范围与用途
BJX系列隔爆型防爆接线箱适用于含有爆炸性气体环境(1区或2区)的场所,在交流50Hz,电压至380V的线路中作为系统动力配电之用。
Series BJX flameproof explosion-proof junction box is suitable for the environment containing explosive gases ( zone 1 or zone 2) place, in the exchange of 50Hz, voltage to 380V line as a system power distribution for.
2.型号含义
B JX- □
额定电流
接线箱
防爆
3.IIC级BJX-20/30 20/60 20/36防爆接线箱主要技术数据见表
型号 | 额定电压 V | 额定电流 A | 防爆等级 | 母线排 | 进出线管径 |
BJX-400 | 220 380 | 400 | ExdⅡBT6 | 4×40 | G2?" |
BJX-600 | 600 | 5×50 | G3?" |
壳体型号 | 型号 | A | B | C | D | E | F | G | H | 进线口数量及规格 | 出线口数量及规格 | 备注 |
Ⅰ型 | BJX-20/20 | 190 | 226 | 274 | 92 | 124 | 238 | 12 | 98 | 1-G1" | 3-G3/4" | ExeⅡT6 |
Ⅱ型 | BJX-20/20 | 190 | 226 | 318.5 | 150 | 190 | 332 | 12 | 98 | 1-G11/2" | 3-G1" | |
Ⅲ型 | BJX-20/30 | 250 | 210 | 378.5 | 190 | 226 | 332 | 12 | 98 | 1-G1/2" | 4-G1" | |
Ⅳ型 | BJX-20/60 | 250 | 351 | 400 | 210 | 250 | 404 | 13 | 98 | 1-G2" | 6-G1" | |
Ⅴ型 | BJX-20/80 | 300 | 351 | 428.5 | 160 | 200 | 354 | 13 | 98 | 2-G2" | 7-G1" | |
Ⅵ型 | BJX-20/120 | 300 | 351 | 429 | 260 | 300 | 454 | 13 | 98 | 2-G2" | 9-G1" |
结构概述
该系列接线箱采用钢板焊接结构,壳盖与壳身之间采用隔爆接合面结构,箱内装有供电缆接线的母线排,箱体上下端设有进出线引入装置。箱体内外均设有接地螺栓。
5使用与维护
5.1 接线箱引入装置的密封圈采用具有一定邵尔硬度橡胶制造,接线后应压紧,使电缆处于良好的密封状态在维修时若发现其老化应与制造厂购买,并及时更换。
52 进线电缆接在互感器前端铜排上负载电缆接在互感器后端,铜排上这样才能使电流通过互感器。
5.3 在维修时须妥善保护隔爆面,并在清理后涂204-1置换型防锈油。